| 2001-08-08 00:00:00 | BUILDING PLAN REVIW |
| | PERMIT # 01050850 |
| | 4650 GEORGIA AVE |
| | CLARK CONSTRUCTION SERVICES |
| | TEL: 848-6061 |
| | |
| | 1)- SBC 104.2.2: ADDITIOAL INFORMATION |
| | REQUIRED, (2) COPIES OF A CURRENT SURVEY |
| | 2)- SHEET A-1 DISCREPANCY, EAST ELEVA- |
| | TION VS. FLOOR PLAN, ELEVATION IS BACK- |
| | WARDS. |
| | 3)- SHEET A-2 SEC.1 & 2 FOUNDATION, SBC |
| | 1804.1.3 THE BOTTOM OF THE FOOTING SHALL |
| | BE A MINIMUM OF 12" BELOW GRADE. |
| | 4)- 2X12 LEDGER SBC 2304.5.2: REQUIRES |
| | ALL WOOD AGAINST CONCRETE OR CEMENT TO |
| | BE PRESSURE TREATED. |
| | 5)- FIRESTOPPING: SHEET A-2/B: |
| | SBC2305.1.4(1) FIREBLOCKING REQUIRED |
| | AT THE CEILING LINE |
| | 6)- SBC 1606. DESIGN CRITERIA SEE CERTI- |
| | FICATION SHEET |
| | 7)- SBC 1606.4.1/ 1707.4.1 ALL GLAZED |
| | OPENINGS WILL REQUIRE EITHER PRODUCT TES |
| | TING FOR LARGE MISSLE RESISTANCE OR |
| | PROVIDE STORM SHUTTER APPROVAL, EITHER |
| | SBCCI OR DADE COUNTY REPORTS ARE ACCEPT- |
| | TED. |
| | 8)- SBC 1606.2.6.2:COMPONENTS & CLADDING |
| | PROVIDE WIND ZONES FOR ALL OPENINGS |
| | INTERIOR & END ZONES,TABLE 1606.2B & |
| | TABLE 1606.2C. |
| | 9)- ROOFING : SBC1503.3.2 ROOFING ASSEM- |
| | BLIES ARE TO COMPLY FOR TESTING IN A |
| | 110MPH WIND ZONE, PROVIDE (2) COPIES |
| | OF THE PRODUCT APPROVAL REPORT. |
| | ROOFING: LOCTED IN A FIRE DISTRICT, ONLY |
| | CLASS A & B MATERIALS ARE TO BE USED. |
| | 10)- SBC 104.2.2 ADDITIONAL INFORMATION |
| | REQUIRED, THE PLANS DO NOT SPECIFY WHAT |
| | USAGE THE MEZANINE IS TO BE USED FOR? |
| | ASSUMED STORAGE WITH THE LIVE LOAD. |
| | THE PLANS WILL NEED TO HAVE THE USAGE |
| | ON THE PLANS TO TAKE THE EXEMPTION TO |
| | VERTICAL ACCESSIBLITY REQUIRED THROUGH |
| | THE FL ACCESSIBILTY CODE. |
| | THE OTHER ISSUE WILL BE IF THE ENTEND- |
| | ED USEAGE IS TO BE STORAGE: |
| | AN EXISTING OR NEW BUILDINGS SHALL NOT |
| | BE OCCUPIED FOR ANY PURPOSE WHICH WILL |
| | CAUSE THE FLOORS THEREOF TO BE LOADED |
| | BEYOND THEIR SAFE CAPACITY. THE BUILDING |
| | OFFICIAL MAY PERMIT OCCUPANCY OF A BUILD |
| | ING FOR MERCANTILE, COMMERCIAL, OR IN- |
| | DUSTRIAL PURPOSES, BY A SPECIFIC BUSSIN- |
| | ESS WHEN HE/SHE IS SATISFIED THAT SUCH |
| | CAPACITY WILL NOT THEREBY BE EXCEEDED. |
| | IN EVERY BUILDING OR PART OF A BUILDING |
| | USED FOR STORAGE, INDUSTRIAL OR |
| | HAZARDOUS PURPOSES, THE SAFE FLOOR LOADS |
| | AS REVIEWED BY THE BUILDING OFFICIAL ON |
| | THE PLAN, SHALL BE MARKED ON THE PLATES |
| | OF APPROVED DESIGN WHICH SHALL BE |
| | SUPPLIED & SECURED BY THE OWNER OF THE |
| | BUILDING IN A CONSPICUOUS PLACE IN EACH |
| | STORY TO WHICH THEY RELATE. SUCH PLATES |
| | SHALL NOT BE REMOVED OR DEFACED, IF LOST |
| | REMOVED OR DEFACED, SHALL BE REPLACED BY |
| | THE OWNER OF THE BUILDING. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561)659-8096 X 8412 |