Plan Review Notes
Plan Review Notes For Permit 01050805
Permit Number 01050805
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-05-16 00:00:001) SMOKE DETECTORS WHEN INSTALLED ARE
 TO BE A MINIMUM OF AT LEAST THREE FEET
 FROM AIR CONDITIONER DIFFUSERS.
 2) FIRE ALARM EQUIPMENT TO BE CLASS A OR
 FULLY ADDRESSABLE.
 3) FIRE ALARM SYSTEM IS TO BE MONITORED
 BY A LICENSED UL LISTED CENTRAL STATION
 APPROVED BY THE FIRE RESCUE DEPARTMENT.
 4) FIRE ALARM SYSTEM TO BE TESTED WITH
 FIRE RESCUE PERSONNEL AFTER
 INSTALLATION.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved