2001-06-12 00:00:00APPROVED WITH PROVISO:
  
 1-FLOOD ZONE "A". NEED TO PROVIDE THE
 ELEVATION CERTIFICATE.
  
 2-CLARIFY FOOTING SIZE. SEE COMMENTS ON
 FOUNDATION PLAN.
  
 3-STORM SHUTTERS INFORMATION IS NOT
 COMPLETE. PROVIDE COMPLETE INFORMATION
 FOR STORM SHUTTERS UNDER A SEPARATE
 PERMIT APPLICATION.
  
 4-TRUSS DRAWINGS:
 A)TRUSS ENGINEER TO HAVE ALL HIS INFO.
 ON THE TRUSS LAYOUT DRAWING AS REQ'D
 BY CHAPTER 471 OF FLORIDA STATUTES.
 B)TRUSS ENGINEER TO UPDATE ALL GENERAL
 TRUSS DETAILS AND PROVIDE HIS INFO. AS
 REQUIRED BY CHAPTER 471 FL STATUTES.
 C)TRUSS DRAWINGS WERE REVIEWED BY WHO?.
 REVIEW STAMP DOESN'T IDENTIFY THE
 ENGINEER OR FIRM WHO DID THE REVIEW.
 D)CLARIFY WHY THERE ARE TWO DIFFERENT
 SIGNATURES ON ENGINEERED TRUSSES IF
 THEY ARE SIGNED BY THE SAME ENGINEER.
  
 NOTE: THESE COMMENTS WERE ADDRESSED
 SEVERAL TIMES BEFORE AND WE STILL
 GET THE SAME MATERIAL. PLEASE,
 AVOID UNNECESSARY RETURNS AND
 DELAYS.