| 2001-07-12 00:00:00 | SECOND CHECKLIST: |
| | 1-STORM SHUTTERS INFORMATION STILL IS |
| | INCOMPLETE. MISSING KEY PLAN AND |
| | PROPER INSTALLATION SCHEDULE. |
| | -PROVIDE COMPLETE INFORMATION OR APPLY |
| | UNDER A SEPARATE PERMIT. |
| | 2-PROVIDE NOTICE OF COMMENCEMENT. |
| | 3-OWES $275.92 FOR LOW VALUATION. PLEASE |
| | PAY ATTACHED RECEIPT. |
| | 4-SEE PLANS FOR COMMENTS AND CORRECT AS |
| | REQUIRED. PLEASE RETURN REVIEWED SET |
| | AFTER CORRECTIONS ARE DONE IN ORDER TO |
| | EXPEDITE THE REVIEW PROCESS. |
| | 5-PROVIDE PRODUCT APPROVAL FOR: |
| | A)DOUBLE ENTRY DOORS AS SHOWN ON PLANS. |
| | B)FRENCH DOORS WITH SIDELITES & TRANSOM |
| | ABOVE SINGLE ASSEMBLY AS SHOWN ON |
| | PLANS. |
| | C)FRENCH DOORS W/ TRANSOM ABOVE SINGLE |
| | ASSEMBLY AS SHOWN ON PLANS. |
| | D)MULLIONS FOR HORIZONTAL ASSEMBLIES. |
| | PRODUCT APPROVAL SUBMITTED IS FOR |
| | VERTICAL APPLICATIONS ONLY. |
| | E)GARAGE "OUTSWING" SIDE DOORS. PRODUCT |
| | APPROVAL SUBMITTED IS FOR "INSWING". |
| | |
| | NOTE: PRODUCT APPROVAL PACKAGE SUBMITTED |
| | IS THE SAME THAT WAS SUBMITTED BEFORE. |
| | COMMENTS FROM MY PREVIOUS CHECKLIST WERE |
| | NOT ADDRESSED. |
| | |
| | 6-UPDATE: |
| | A)RINKER LETTER FOR MASONRY UNITS. |
| | B)ENGINEERING SPECS FOR PRECAST LINTELS |
| | SIGNED, SEALED AND DATED AS REQUIRED |
| | BY CHAPTER 471 OF FLORIDA STATUTES. |