| Plan Review Notes For Permit 01050716 |
| Permit Number |
01050716 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2001-11-06 00:00:00 | ************** UNSAT ******************* | | | | | | | | | 1)NOTE: PLEASE NOTE THAT PER FS/FAC | | | 61G15-23.002. THE 8 1/2 X 11`S NEED TO | | | HAVE ENGINEERS TITLE BLOCK ON SHEETS. | | | | | | 2)NOTE: PLEASE NOTE MISSING AIC RATINGS | | | FOR PANELS, P1,P2,AND P. | | | | | | 3)NOTE: PLEASE NOTE MISSING PANEL | | | INFORMATION FOR P2. | | | | | | 4)NOTE: PLEASE NOTE MISSING CWP ON | | | GROUNDING ELECTRODE SYSTEM. 250-50. | | | PLEASE NOTE THAT THE ELECTRICAL | | | INSPECTOR MENTIONED GAS LINE BEING | | | ON SYSTEM? PLEASE CLARFIY. | | | | | | 5)NOTE: PLEASE NOTE HANDWRITTEN CHANGES | | | ON PLANS NEED TO BE PRINTED. | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. IF | | | THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|