2001-05-29 00:00:00PLUMBING PLAN REVIEW"DENIED"
 (1) SHT-1 NUMBER ROOMS,AS PER FINISH
 SCHEDULE ON SHT-2.
 (2) SHT 1 EXISTING REST RM'S MEN'S
 WOMEN'S,COMPLY W/FACBC 97 SEC 4.16(2)
 ALTERATIONS TO AN AREA CONTAINING A PRIM
 ARY FUNCTION, THE PATH OF TRAVEL AND THE
 REST RM'S SERVING THE ALTERED AREA,
 ARE READLY ACCESSIBLE AND USEABLE BY
 INDIVIDUALS WITH DISABILITIES.
 SHOW CALCULATIONS FOR A BEAUTY SHOP.FOR
 MINIMUM FACILITIES,SPC 94 SEC 407.1.3
 (3) ALL REST RM FACILITIES IN COMMON
 AREA TO COMPLY W/FACBC 97 SEC 4.1.3.(11)
 (4) BREAK RM SINK TO COMPLY W/FACBC
 4.24.2,4.24.5 HEIGTH,KNEE CLEARANCE.
 (5) SHT 8 SEE GAS PERMIT APPLICATION
 REQUIRMENTS ATTACHED, ADDRESS EA ITEM.
 (6) SHT-8 FUTURE F/D TO HAVE A DEEP
 SEAL TRAP OR TRAP PRIMER SPC 97 409.1.1
 (7) SHT-8 2" CROSS NOT PERMITED ON A
 WASHING MAHINE WASTE,SEC 409.12.3
 (8) SHT-8 WATER SUPPLY, NO MORE 2 PLBG
 FIXTURES SHALL BE SUPPLIED W/ 1/2" COLD
 WATER SUPPLY, NO MORE THAN 4 PLBG.
 FIXTURES SHALL BE SUPPLIED W/ 1/2" HOT
 WATER SUPPLY. SEC 607.7 PBC AMEND SPC 94
 (9) SHT-8 DWV ISOMETRIC,SHOW ALL PIPE
 SIZES.SPC 94 SEC 104.3
 (10) WATER SUPPLY,EA TENANT SPACE TO
 HAVE A SEPERATE BACK FLOW PREVENTER.
 SPC 94 SEC 606.
 (11) SHT-8 PROVIDE CUT SHTS ON WASHING
 MACHINES,TO SHOW THAT A LINT SEPERATOR
 IS NOT REQUIRED.SPC 94 SEC 1004.10.1
 END OF COMMENTSPAUL SCHMITZ