Plan Review Notes
Plan Review Notes For Permit 01050716
Permit Number 01050716
Review Stop M
Sequence Number 1
Notes
Date Text
2001-06-07 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
  
 1.O.A. CALCULATIONS PER ASHRAE 62-89
 AND AIR BALANCE SCHEDULE AS PER 1997
 SMC 501.2.
  
 2.NO A/C DROP IN PRIVATE RESTROOM HOW
 IS AIR MAKE UP BEING SUPPLIED.
  
 3.PLAN SHEET 5 & 6 INDICATE A WALL
 BETWEEN LOBBY & WAITING ROOM, PLEASE
 CORRECT.
  
 4.A/C FOR ROOM 20 IS MISSING DUCT AND
 GRILL SIZE.
  
 5.PLEASE PROVIDE MANUFACTURER CUT
 SHEET FOR CONDENSER UNIT STANDS.
 (18" MIN. FROM ROOF SURFACE TO
 BOTTOM OF SUPPORT RAIL.)
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.