| Plan Review Notes For Permit 01050716 |
| Permit Number |
01050716 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-06-07 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | | | | 1.O.A. CALCULATIONS PER ASHRAE 62-89 | | | AND AIR BALANCE SCHEDULE AS PER 1997 | | | SMC 501.2. | | | | | | 2.NO A/C DROP IN PRIVATE RESTROOM HOW | | | IS AIR MAKE UP BEING SUPPLIED. | | | | | | 3.PLAN SHEET 5 & 6 INDICATE A WALL | | | BETWEEN LOBBY & WAITING ROOM, PLEASE | | | CORRECT. | | | | | | 4.A/C FOR ROOM 20 IS MISSING DUCT AND | | | GRILL SIZE. | | | | | | 5.PLEASE PROVIDE MANUFACTURER CUT | | | SHEET FOR CONDENSER UNIT STANDS. | | | (18" MIN. FROM ROOF SURFACE TO | | | BOTTOM OF SUPPORT RAIL.) | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|