2001-05-16 00:00:001) GAS INSTALLATIONS TO COMPLY WITH
 NFPA 54, THE NATIONAL FUEL GAS CODE.
 2) IT APPEARS THAT ADDITIONAL EMERGENCY
 LIGHTING FIXTURES ARE NEEDED THROUGHOUT
 THE SPACE.
 3) PLEASE PROVIDE OCCUPANT LOAD COUNT.
 4) DUCT SMOKE DETECTORS REQUIRED IN ALL
 AIR HANDLING SYSTEMS OVER 2000 CFM. WHEN
 ACTIVATED, THE AIR HANDLING EQUIPMENT IS
 TO SHUT DOWN AND PROVIDE AN AUDIBLE AND
 VISUAL ALERT.
 5) BUILDING ADDRESS REQUIRED PER CITY
 CODE REQUIREMENTS.
 6) NO INTERIOR FINISH INFORMATION
 PROVIDED WITH PLANS.
 7) PLEASE INDICATE HOW DRYER VENTS
 TERMINATE.
  