| Plan Review Notes For Permit 01050716 |
| Permit Number |
01050716 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-05-16 00:00:00 | 1) GAS INSTALLATIONS TO COMPLY WITH | | | NFPA 54, THE NATIONAL FUEL GAS CODE. | | | 2) IT APPEARS THAT ADDITIONAL EMERGENCY | | | LIGHTING FIXTURES ARE NEEDED THROUGHOUT | | | THE SPACE. | | | 3) PLEASE PROVIDE OCCUPANT LOAD COUNT. | | | 4) DUCT SMOKE DETECTORS REQUIRED IN ALL | | | AIR HANDLING SYSTEMS OVER 2000 CFM. WHEN | | | ACTIVATED, THE AIR HANDLING EQUIPMENT IS | | | TO SHUT DOWN AND PROVIDE AN AUDIBLE AND | | | VISUAL ALERT. | | | 5) BUILDING ADDRESS REQUIRED PER CITY | | | CODE REQUIREMENTS. | | | 6) NO INTERIOR FINISH INFORMATION | | | PROVIDED WITH PLANS. | | | 7) PLEASE INDICATE HOW DRYER VENTS | | | TERMINATE. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|