| Notes |
| Date |
Text |
| 2001-06-06 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT LOAD | | | CALCULATIONS NEED TO BE COMPLETED. | | | PLEASE SHOW | | | ALL CONTINUOUS LOADS AT 125% 230-42 AND | | | 215-3. | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | PLEASE NOTE THAT AIC RATINGS WERE SUB- | | | -MITTED FOR PANELS BUT NOT FOR MAIN | | | DISCONNECTS. ARE MAIN DISC`S FUSED? | | | WHICH NOTE 16 WOULD PERTAIN TO? | | | PLEASE CLARIFY. | | | | | | 3)NOTE: PLEASE PROVIDE CLARIFICATION | | | ON CONDUIT TYPE BETWEEN MAIN AND PANELS. | | | DOES NOTE 10 PERTIAN TO CONDUIT FROM | | | MAIN TO PANEL? PLEASE CLARIFY. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|