| 2001-06-04 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 01050716 |
| | 2511 S DIXIE HWY |
| | MONARD CONST 758-0362 |
| | ARCH ROBERT BELL 683-9133 |
| | |
| | 1)- FL. ACC. CODE 1997 SEC. 416.2.2 |
| | DISPROPORTIONATE COST ALTERATIONS MADE |
| | TO PROVIDE AN ACCESSIBLE PATH OF TRAVEL |
| | TO ALTERED AREAS SHALL BE DEEMED DISPRO- |
| | PORTIONAE TO THE OVERALL ALTERATION WHEN |
| | THE COST EXCEEDS 20% OF THE COST OF THE |
| | ALTERATION TO THE PRIMARY FUNCTION AREA. |
| | 416.1 (C) IF ALTERATIONS OF SINGLE |
| | ELEMENTS, WHEN CONSIDERED TOGETHER, |
| | AMOUNT TO AN ALTERATIOIN OF A ROOM OR |
| | SPACE IN A BUILDING OR FACILITY, THE |
| | ENTIRE SPACE SHALL BE MADE ACCESIBLE. |
| | |
| | 2)- SBC 1204.2 SURROUNDING WALLS & |
| | FLOORS OF ALL PUBLIC RESTROOMS SHALL BE |
| | LINED WITH NONABSORBANT MATERIALS TO A |
| | HEIGTH OF 4'-0" . |
| | |
| | 3)- RAMP LOCATED IN FRONT OF THE WOMENS |
| | RESTROOM WHAT IS THE CHANGE INGRADE? |
| | WILL HANDRAILS BE REQUIRED? |
| | |
| | 4)- SBC 104.2.2 ADD. INFORMATION. USEAGE |
| | OF ROOMS 9/10 FOR FUTURE FLOOR DRAINS? |
| | |
| | 5)- SHEET #1 NOTE INDICATES NEW WINDOWS, |
| | DETAILS FOR WINDOW BUCK ATTACHMENT SBC |
| | 1606.2.6.2 AND PRODUCT APPROVAL FOR SUCH |
| | GLAZED OPENINGS TEST PRESSURES AT 1 1/2 |
| | THE DESIGN PRESSURE, ALSO LARGE MISSLE |
| | IMPACT TESTING OR STORM SHUTTERS WITH |
| | APPROVED LARGE MISSLE IMPACT TESTING. |
| | SBCCI REPORT OR DADE COUNTY PRODUCT |
| | APPROVAL TESTING REPORTS ARE ACCEPTABLE. |
| | |
| | 6)- SSBC TABLE 803.3 REQUIRES A MINIMUM |
| | FINISH SCHEDULE BASED ON OCCUPANCY, |
| | FOR SPRINKLERED AND NONSPRINKLERED |
| | OCCUPANCIES. |
| | |
| | 7)- SBC 104.2.2 ADD INFORMATION REQUIRED |
| | DETAILS 1/3, 2/3 INDICATE A RESTRAUNT IN |
| | ONE OF THE ADJACENT TENANT SPACES, WHAT |
| | IS THE SQ. FOOTAGE OF SPACE? 100 OCC. |
| | LOAD REQUIRES A 2 HR WALL WHICH IS INDIC |
| | ATED ON THE PLAN, WHERE AS YOU INDICATE |
| | 1 HR SEPERATION REQUIRED? GIVE GYPSUM OR |
| | UL RATING OF WALLS. |
| | |
| | 8)- FIRE CAUKING PENETRATIONS SBC 705.1 |
| | (2) SHOW MAN SPEC FOR VERTICAL APPLICA- |
| | TION. |
| | |
| | BUILDING PLAN REVIEW. |
| | JIM WITMER |
| | (561) 659- 8096 EX 8412 |