| 2001-05-15 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE CLARIFY SERVICE. THERE | | | ARE PARTS OF RISER DIAGRAM THAT IS | | | SHOWN AS EXISTING? METERCAN AND FEEDERS? | | | YET PANELS AND TRANSFORMER ?? | | | IF NEW EQUIPMENT IS BEING INSTALLED, | | | PLEASE CLARIFY. | | | PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | IF THE EQUIPMNET IS NEW THEN PLANS MUST | | | ALSO BE SIGNED AND SEALED BY AN P.E. | | | PER 553-79-6A UNDER THE F.A.C. | | | | | | 2)NOTE: PLEASE CLARIFY CIRCUIT#`S FOR | | | NEW LIGHTING SHOWN? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | CLARIFICATION. IF THERE ARE ANY QUESTION | | | -S, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|