Plan Review Notes
Plan Review Notes For Permit 01050650
Permit Number 01050650
Review Stop P
Sequence Number 1
Notes
Date Text
2001-05-22 00:00:00REVEIW NOTES: FAILED
  
 1) SHOW DISTANCE TO MOST REMOTE OUTLET.
  
 2) CALCULATIONS FOR COMBUSTION AIR.
  
 3) TYPE, LOCATION, SIZE AND TERMINATION
 PT. OF GAS VENTS.
  
 4) SUBMIT MORE INFORMATION/ISOMETRIC
 DRAWING ON AIR INTAKE AND EXHAUST PIPING
 FOR WATER HEATERS. (SEE SHT. P-3)
  
 5) IS PIPE (3") GOING TO BE WELD PIPE
 OR SCREW PIPE?
  
 REVIEW BY KEN STEVENS (561) 659-8096
 EXT. 8377