| Notes |
| Date |
Text |
| 2001-08-02 00:00:00 | 1) MONITORING OF THE FIRE ALARM AND | | | FIRE SPRINKLER SYSTEM ARE NOT OPTIONAL. | | | BOTH SYSTEMS MUST BE MONITORED BY A | | | LICENSED UL LISTED CENTRAL STATION | | | APPROVED BY THE FIRE RESCUE DEPARTMENT. | | | 2) COMBINATION BURGLAR AND FIRE ALARM | | | SYSTEMS ARE TO MEET NFPA 72 REQUIREMENTS | | | 2-4.7.2 | | | 3) DUCT SMOKE DETECTORS WHEN ACTIVATED | | | SHALL AUTOMATICALLY SHUT DOWN AIR | | | HANDLING UNITS AND CAUSE THE FIRE ALARM | | | SYSTEM TO SOUND. | | | 4) SMOKE DETECTORS SHALL BE LOCATED | | | FARTHER THAN THREE FEET FROM AIR | | | CONDITIONER DIFFUSERS. | | | 5) LOCKS ON EXIT DOORS SHALL BE FAIL | | | SAFE AND NOT FAIL SECURE. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096, EXT.8497 | | | 835-2910 |
|