Plan Review Notes
Plan Review Notes For Permit 01050623
Permit Number 01050623
Review Stop FIRE
Sequence Number 4
Notes
Date Text
2001-08-02 00:00:001) MONITORING OF THE FIRE ALARM AND
 FIRE SPRINKLER SYSTEM ARE NOT OPTIONAL.
 BOTH SYSTEMS MUST BE MONITORED BY A
 LICENSED UL LISTED CENTRAL STATION
 APPROVED BY THE FIRE RESCUE DEPARTMENT.
 2) COMBINATION BURGLAR AND FIRE ALARM
 SYSTEMS ARE TO MEET NFPA 72 REQUIREMENTS
 2-4.7.2
 3) DUCT SMOKE DETECTORS WHEN ACTIVATED
 SHALL AUTOMATICALLY SHUT DOWN AIR
 HANDLING UNITS AND CAUSE THE FIRE ALARM
 SYSTEM TO SOUND.
 4) SMOKE DETECTORS SHALL BE LOCATED
 FARTHER THAN THREE FEET FROM AIR
 CONDITIONER DIFFUSERS.
 5) LOCKS ON EXIT DOORS SHALL BE FAIL
 SAFE AND NOT FAIL SECURE.
  
 CAPTAIN MIKE CARSILLO
 659-8096, EXT.8497
 835-2910