| 2001-05-17 00:00:00 | *******************PROVISO************** | | | | | | APPROVED 12/26/00 ON MASTER PERMIT #0004 | | | 0884 WITH THE FOLLOWING PROVISO. | | | | | | 1.RE: NOTE ON SHAFT REMOVAL ORTO | | | MODIFICATION, 1997 SMC 610.4 - | | | DUCTS EXTENDING THROUGH MORE THAN | | | ONE FLOOR TO BE PROTECTED BY SHAFT | | | ENCLOSURE HAVING A FIRE RESISTANCE | | | NOT LESS THAN 2 HRS FOR A BUILDING | | | 4 STORIES AND MORE IN HEIGHT.PLAN | | | UNCLEAR AS TO WHAT WILL BE CHANGED. | | | THIS CODE SHALL BE COMPLIED WITH | | | FOR ANY CHANGES. | | | | | | 2.LOCAL AMENDMENT 304.2.5 REQUIRES A | | | MINIMUM 18" CLEARENCE BETWEEN ROOF | | | SURFACE AND BOTTOM OF SUPPORT | | | STRUCTURE OF STAND.PLAN INDICATES | | | EXPIRED DADE CO. APPROVAL. | | | | | | 3.NOTE 5 AND 6 SHOW OUTSIDE AIR AND | | | EXHAUST AIR NEXT TO EACH OTHER. | | | CODE REQUIRES A 10 FT SEPARATION | | | BETWEEN THE TWO. (1997 SMC 506.1) | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096EXT. 8388. |
|