| Notes |
| Date |
Text |
| 2001-06-01 00:00:00 | PLUMBING PLAN REVIEW PROVISO: | | | (1) NOTES ON SHT'S A-2 P-1,P-2 AS PER | | | ARCHETICT MR EDWARD GHEEZI,305-596-3800 | | | (2) SHT P-1 SPC 94 CURRENT CODE. | | | (3) SHT P-2 3 COMP SINK WASTE NO RUNNING | | | TRAPS, INDIVIDUAL TRAPS FOR EA COMPART- | | | MENT.SPC 94 SEC 1003. | | | (4) SHT P-1 MATERIAL FOR DWV SYSTEM | | | SCH 40 PVC PIPE.ABOVE,BELOW GRADE. | | | (5) SHT P-2 AIR CHAMBERS DELETED,SCHOCK | | | ARRESTOR LOCATION BY ENG. OF RECORD. | | | (6) NO GAS APPLIANCES SHOWN ON SHT K-1. | | | END OF CIMMENTSPAUL SCHMITZ | | | QUESTIONS 561-659-8096 X 8233 |
|