| Plan Review Notes For Permit 01050533 |
| Permit Number |
01050533 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-05-18 00:00:00 | DENIED; | | | | | | HANDICAP LAVATORIES CLEARANCES SHALL | | | COMPLY WITH 97 FACBC FIG. 32. CLEAR | | | FLOOR SPACE IS 15" FROM WALL TO CENTER | | | OF LAV. | | | | | | PAGE P-1 PLUMBING NOTES. PLUMBING CODE | | | USED IS THE 94 STANDARD PLUMBING CODE. | | | | | | SPECIFY MATERIAL TO BE USED FOR DRAINAGE | | | PIPE. | | | | | | 3 COMPARTMENT SINK D192 SHALL BE | | | INDIRECTLY WASTED PER.804.1. | | | | | | WATER HEATER TO BE READILY ACCESSIBLE. | | | LOCATE ON FLOOR OR INSTALL A PERMINATE | | | FIXED SHIPS LADDER. | | | | | | SPECIFY TYPE AND SIZE OF SHOCK ARRESTERS | | | TO BE USED AND SHOW LOCATION ON WATER | | | RISER DIAGRAM. | | | | | | GAS DRAWINGS REQUIRED FOR GAS EQUIPMENT | | | TO BE USED. FOLLOW ATTACHED, GAS PERMIT | | | APPLICATION REQUIREMENTS SHEET. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8369 |
|