| Plan Review Notes For Permit 01050533 |
| Permit Number |
01050533 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-06-06 00:00:00 | ********************DENIED************** | | | | | | AIR BALANCE SCHEDULE ON DRAWING M-1 | | | REFLECTS TWO AC#3. | | | | | | AIR DISTRIBUTION ON PLAN - 6 DROPS AT | | | 465 CFM IS 2790 CFM, BOTH AIR BALANCE | | | SCHEDULE AND ROOF TOP A.C. UNIT | | | SCHEDULE REFLECT 2400 CFM. PLEASE | | | CORRELATE. | | | | | | NOTE:18" MINIMUM FROM ROOF SURFACE TO | | | BOTTOM OF SUPPORT RAIL. | | | | | | ADDITIONAL MECHANICAL PERMITS AND PLANS | | | REQUIRED FOR WALK-IN COOLERS, KITCHEN | | | HOODS/EXHAUST AND FIRE SUPRESSION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT.8388. |
|