2001-06-06 00:00:00********************DENIED**************
  
 AIR BALANCE SCHEDULE ON DRAWING M-1
 REFLECTS TWO AC#3.
  
 AIR DISTRIBUTION ON PLAN - 6 DROPS AT
 465 CFM IS 2790 CFM, BOTH AIR BALANCE
 SCHEDULE AND ROOF TOP A.C. UNIT
 SCHEDULE REFLECT 2400 CFM. PLEASE
 CORRELATE.
  
 NOTE:18" MINIMUM FROM ROOF SURFACE TO
 BOTTOM OF SUPPORT RAIL.
  
 ADDITIONAL MECHANICAL PERMITS AND PLANS
 REQUIRED FOR WALK-IN COOLERS, KITCHEN
 HOODS/EXHAUST AND FIRE SUPRESSION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT.8388.