| Plan Review Notes For Permit 01050516 |
| Permit Number |
01050516 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-05-14 00:00:00 | 1) STAIR SECTION INDICATES 10" TREADS. | | | PLEASE BE ADVISED 11" TREADS ARE | | | REQUIRED. | | | 2) PLEASE INDICATE THE TYPE OF STORAGE | | | THAT WILL OCCUR IN THE POOL STORAGE | | | AREA. | | | 3) ELECTRICAL FLOOR PLAN DOES NOT | | | INDICATE EXIT SIGNAGE OR EMERGENCY | | | LIGHTING. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|