| Plan Review Notes For Permit 01050459 |
| Permit Number |
01050459 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-07-09 00:00:00 | DENIED | | | | | | 1) PAGE A-1, STILL DO NOT HAVE CLEAR | | | FLOOR SPACE FOR LOUNGE SINK. 30" X 48" | | | REQUIRED. IF FRONT APPROACH, 30" X 19" | | | CLEAR UNDER COUNTER REQUIRED. SHOW | | | DETAIL. | | | | | | 2) PAGE A-1, MEN & WOMENS RESTROOMS, | | | 5' TURNING RADIUS REQUIRED OUTSIDE OF | | | STALL. DOORS CAN NOT OPEN INTO CLEAR | | | FLOOR SPACE. | | | | | | 3) PAGE PO-1 DOMESTIC WATER RISER DIA- | | | GRAM, WATER HAMMER ARRESTORS MUST BE IN- | | | STALLED PER MANUFACTURE INSTALLATION IN- | | | STRUCTIONS. PLEASE SEE ATTACHED SHEET. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|