Plan Review Notes
Plan Review Notes For Permit 01050459
Permit Number 01050459
Review Stop P
Sequence Number 1
Notes
Date Text
2001-06-09 00:00:00PLUMBING PLAN REVIEW"DENIED"
 (1) SHT A1 COMPLY W/FACBC 97,4.1.6(1)(B)
 ACCESSIBLE BUILDING ALTERATIONS.
 (2) SHT A4 REST RM 121 & 122,DETAIL#5,10
 H/C,W/C,DIMENSION OFF WALL 19",FACBC 97
 COMLPY WITH FIG 28, 18" OFF THE WALL.
 (3) SHT A4,RM 121 LAVATORIES, MIRRORS,
 COMPLY W/FACBC 97 SEC 4.19.
 URINALS COMPLY W/FACBC SEC 4.18.2 & .3
 HGTH TO LIP OF URI 17" TO FF. CLEAR FLR
 SPACE,30" X 48".
 (4) SHT P0.1,DOMESTIC WATER ISOMETRIC &
 NOTES 13,18, REFERENCE, AIR CHAMBERS.
 SHOW A DETAIL OF AN APPROVED AIR CHAMBER
 AND HOW IT WILL BE ACCESSIBLE,RECHARGE-
 ABLE. SPC 94 SEC 607.8.3
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096X8233