| Plan Review Notes For Permit 01050459 |
| Permit Number |
01050459 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-06-09 00:00:00 | PLUMBING PLAN REVIEW"DENIED" | | | (1) SHT A1 COMPLY W/FACBC 97,4.1.6(1)(B) | | | ACCESSIBLE BUILDING ALTERATIONS. | | | (2) SHT A4 REST RM 121 & 122,DETAIL#5,10 | | | H/C,W/C,DIMENSION OFF WALL 19",FACBC 97 | | | COMLPY WITH FIG 28, 18" OFF THE WALL. | | | (3) SHT A4,RM 121 LAVATORIES, MIRRORS, | | | COMPLY W/FACBC 97 SEC 4.19. | | | URINALS COMPLY W/FACBC SEC 4.18.2 & .3 | | | HGTH TO LIP OF URI 17" TO FF. CLEAR FLR | | | SPACE,30" X 48". | | | (4) SHT P0.1,DOMESTIC WATER ISOMETRIC & | | | NOTES 13,18, REFERENCE, AIR CHAMBERS. | | | SHOW A DETAIL OF AN APPROVED AIR CHAMBER | | | AND HOW IT WILL BE ACCESSIBLE,RECHARGE- | | | ABLE. SPC 94 SEC 607.8.3 | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|