Plan Review Notes
Plan Review Notes For Permit 01050459
Permit Number 01050459
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-05-15 00:00:001) INTERIOR FINISH TO BE AT LEAST CLASS
 "C" ON WALLS AND CEILINGS.
 2) FIRE ALARM NOTES INDICATES THAT FIRE
 ALARM CIRCUITS TO BE CLASS B, STYLE C.
 ONLY CLASS A, STYLE D CIRCUITS WILL
 BE PERMITTED.
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER REMODEL.
 4) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM EQUIPMENT INSTALLATION.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910