| Plan Review Notes For Permit 01050459 |
| Permit Number |
01050459 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-05-15 00:00:00 | 1) INTERIOR FINISH TO BE AT LEAST CLASS | | | "C" ON WALLS AND CEILINGS. | | | 2) FIRE ALARM NOTES INDICATES THAT FIRE | | | ALARM CIRCUITS TO BE CLASS B, STYLE C. | | | ONLY CLASS A, STYLE D CIRCUITS WILL | | | BE PERMITTED. | | | 3) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE SPRINKLER REMODEL. | | | 4) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE ALARM EQUIPMENT INSTALLATION. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|