Plan Review Notes
Plan Review Notes For Permit 01050453
Permit Number 01050453
Review Stop E
Sequence Number 1
Notes
Date Text
2001-05-15 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE CLARIFY PANEL LOCATION.
 PLANS REFERENCE TO CIRCUIT GOING TO
 PANEL?
  
 2)NOTE: PLEASE NOTE THAT MEANS OF DISC-
 -CONNECT FOR POWER IS REQ`D AT DETACHED
 STRUCTURE. PER 225.31 THIS CAN BE AS
 LITTLE AS A SINGLE POLE SWITCH IF ONLY
 ONE CIRCUIT? PLEASE SHOW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372