| Plan Review Notes For Permit 01050453 |
| Permit Number |
01050453 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-05-15 00:00:00 | ***************** UNSAT ************** | | | | | | 1)NOTE: PLEASE CLARIFY PANEL LOCATION. | | | PLANS REFERENCE TO CIRCUIT GOING TO | | | PANEL? | | | | | | 2)NOTE: PLEASE NOTE THAT MEANS OF DISC- | | | -CONNECT FOR POWER IS REQ`D AT DETACHED | | | STRUCTURE. PER 225.31 THIS CAN BE AS | | | LITTLE AS A SINGLE POLE SWITCH IF ONLY | | | ONE CIRCUIT? PLEASE SHOW. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|