Plan Review Notes
Plan Review Notes For Permit 01050406
Permit Number 01050406
Review Stop P
Sequence Number 1
Notes
Date Text
2001-05-12 00:00:00DENIED;
  
 1.DRINK FOUNTAIN SHALL BE INSTALLED, A
 WATER COOLER IS NOT A PLUMBING FIXTURE
  
 2.DRINKING FOUNTAIN TOO COMPLY WITH 97
 FACBC SEC. 4.13(10) AND 4.15 (D.F. TO
 ACCESSIBLE FOR PEOPLE IN WHEEL CHAIRS
 AND PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.
  
 3.HANDICAP BATH NOT TO FACBC SPECIFICA-
 TIONS. BATHROOM NOT LARGE ENOUGH.
 INLARGE AND SHOW TURNING RADIUS ON
 PLANS.
  
 4.LOUNG SINK TO COMPLY WITH FACBC 4.24.1
 THRU 4.24.7.
  
 5.AIR CHAMBERS TO COMPLY WITH 94 SPC
 607.8.2 AND 607.8.3. ENGINEERED WATER
 HAMMER ARRESTERS SHOULD BE SPECIFIED
 BY ENGINEER OF RECORD.
  
 6.PLUMBING FIXTURE SCHEDULE SHOWS
 HANDICAP FIXTURES IN STAFF BATHROOM.
 STAFF BATHROOM DOES NOT MEET FACBC
 SPECIFCATIONS.
  
 7.WATER RISER. ONLY 2 FIXTURES PERMITED
 ON 1/2" COLD WATER LINE. 97 COUNTY-
 WIDE AMENDMENTS 607.7.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8369