| 2001-05-12 00:00:00 | DENIED; | | | | | | 1.DRINK FOUNTAIN SHALL BE INSTALLED, A | | | WATER COOLER IS NOT A PLUMBING FIXTURE | | | | | | 2.DRINKING FOUNTAIN TOO COMPLY WITH 97 | | | FACBC SEC. 4.13(10) AND 4.15 (D.F. TO | | | ACCESSIBLE FOR PEOPLE IN WHEEL CHAIRS | | | AND PEOPLE WHO HAVE TROUBLE BENDING | | | OR STOOPING. | | | | | | 3.HANDICAP BATH NOT TO FACBC SPECIFICA- | | | TIONS. BATHROOM NOT LARGE ENOUGH. | | | INLARGE AND SHOW TURNING RADIUS ON | | | PLANS. | | | | | | 4.LOUNG SINK TO COMPLY WITH FACBC 4.24.1 | | | THRU 4.24.7. | | | | | | 5.AIR CHAMBERS TO COMPLY WITH 94 SPC | | | 607.8.2 AND 607.8.3. ENGINEERED WATER | | | HAMMER ARRESTERS SHOULD BE SPECIFIED | | | BY ENGINEER OF RECORD. | | | | | | 6.PLUMBING FIXTURE SCHEDULE SHOWS | | | HANDICAP FIXTURES IN STAFF BATHROOM. | | | STAFF BATHROOM DOES NOT MEET FACBC | | | SPECIFCATIONS. | | | | | | 7.WATER RISER. ONLY 2 FIXTURES PERMITED | | | ON 1/2" COLD WATER LINE. 97 COUNTY- | | | WIDE AMENDMENTS 607.7. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8369 |
|