2001-06-04 00:00:00DENIED
 PROVIDE INFORMATION ON ROOF ATTACHMENT
 FOR RTU'S
 FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 REQUIRED FOR BOTH UNITS
 RTU 2 APPEARS TO SERVE PROCEDURE ROOM.
 PROVIDE RETURN AIR PATH TO UNIT FROM
 THIS SPACE ( ALL AREAS WITH 300 CFM OR
 MORE REQUIRE RETURN AIR TO UNIT.
 PROVIDE INFORMATION ON BATHROOM EXHAUST
 AS REQUIRED BY CODE
 PROVIDE OUTSIDE AIR SCHEDULE SHOWING
 COMPLIANCE WITH ASHRAE 62-89
 HOW DOES RTU 2 S/A DUCT ATTACH TO S/A
 DUCT IN SPACE?
 DUCT WITH 2 PIECE 90'S WILL REQUIRE
 TURNING VANES OR MAKE AS 3 PIECE 90'S.
  