| Plan Review Notes For Permit 01050336 |
| Permit Number |
01050336 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-05-23 00:00:00 | *******************DENIED*************** | | | | | | | | | 1.PROVIDE OUTSIDE AIR CALCULATIONS | | | (ASHRAE 62-89) AND AIR BALANCE | | | SCHEDULE AS PER 1997 SMC 501.2. | | | | | | 2.DRAWING M2.1 INDICATES EXISTING R/A | | | GRILLES TO REMAIN, ARE THEY BEING | | | USED FOR SUPPLY AS INDICATED ON | | | M2.2?ALSO, IS THIS WALL FIRE | | | RATED? | | | | | | 3.PLEASE PROVIDE INFORMATION ON THE | | | EXISTING EXHAUST FAN IN THE BATTERY | | | ROOM.HOW MANY CFM'S WILL IT BE | | | REMOVING AND DOES IT RUN CON- | | | TINUOUSLY? | | | | | | 4.NO COMBUSTIBLES ABOVE THE CEILING | | | IN THE RETURN AIR PLENUM. | | | | | | 5.PLEASE ADDRESS HOW THE REMAINING | | | "STORAGE" AREA IS BEING VENTILATED. | | | | | | NOTE:ADDITIONAL PLANS AND PERMIT | | | REQUIRED FOR FUEL OIL TANK. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|