2001-05-15 00:00:001) FIRE HYDRANTS LOCATED ALONG THE WEST
 SIDE OF THE CONVENTION CENTER ALONG THE
 DELIVERY AREA MUST NOT BE BLOCKED BY
 THE CMU RETAINING WALL. THE FIRE
 HYDRANTS MUST BE LOCATED ON THE EAST
 SIDE OF THE RETAINING WALL. THE
 RETAINING WALL MUST NOT INTERFERE WITH
 THE OPERATION OF ANY FIRE HYDRANT
 LOCATED ALONG THE WEST SIDE OF THE
 CONVENTION CENTER.
 2) UNDEGROUND FIRE MAINS TO BE LISTED
 FOR FIRE PROTECTION SERVICE AND COMPLY
 WITH NFPA 24, THE STANDARD FOR FIRE
 SERVICE MAINS AND THEIR APPURTENANCES.
 ALL UNDERGOUND FIRE MAINS ARE TO BE
 PRESSURE TESTED AT 200 LBS. FOR TWO
 HOURS PER NFPA 24.
 3) WET FIRE HYDRANTS ARE TO BE PROVIDED
 PRIOR TO, DURING AND AFTER CONSTRUCTION
 OF THE CONVENTION CENTER.
 4) THE CHAIN LINK GATES ARE TO PROVIDE
 AT LEAST TWENTY FEET IN CLEAR WIDTH FOR
 FIRE RESCUE ACCESS.
 5) ADDITIONAL FIRE HYDRANTS ARE REQUIRED
 ALONG FLORIDA AVENUE. PRESENTLY THE
 PLANS ONLY SHOW ONE HYDRANT ON THE NORTH
 SIDE NEAR OKEECHOBEE BOULEVARD. THESE
 ADDITONAL FIRE HYDRANTS ARE TO BE
 STAGGERED ON THE EAST AND WEST SIDES OF
 THE PROPOSED FIVE LANE ROADWAY.
 6) TAMPER SWITCHES,CHAINS AND LOCKS WILL
 BE REQUIRED FOR BACKFLOW DEVICES USED
 FOR FIRE MAINS.
 7) ALL EXTERIOR STAIRS TO BE SLIP
 RESISTANT.
 8) STAIRS TO COMPLY WITH NEW STAIR
 REQUIREMENTS FROM NFPA 101, THE LIFE
 SAFETY CODE.
 9) PIPE BOLLARDS ARE TO NOT TO INTERFERE
 WITH THE SAFE USAGE OF ANY STAIRS.
 10) HANDRAILS AND GUARDS TO COMPLY WITH
 NFPA 101, THE LIFE SAFETY CODE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910