| Plan Review Notes For Permit 01050312 |
| Permit Number |
01050312 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-05-10 00:00:00 | REVIEW NOTES:FAILED | | | | | | 1) SUBMIT FULL SET OF PLANS PER SBC-97 | | | 104.2.1. ONE SET HAS 7 OF 9 PAGES AND | | | THE OTHER ONE HAS 8 OF 9 PAGES. | | | | | | 2) SANITARY RISER DOES NOT COMPLY WITH | | | SPC-94 CODE. SUBMIT SANITARY RISER | | | DIAGRAM THAT REFLECTS FLOOR PLAN. | | | SIZE PIPE TO COMPLY WITH TABLE 714.1 | | | | | | REVIEW BY KEN STEVENS (561) 659-8096 | | | EXT. 8377 |
|