Plan Review Notes
Plan Review Notes For Permit 01050312
Permit Number 01050312
Review Stop E
Sequence Number 1
Notes
Date Text
2001-05-14 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT PLANS THAT
 CONTAIN TITLE BL0CK, MUST BE BE SIGNED
 AND SEALED BY THAT ARCH/ENGINEER OF
 RECORD. PER F.A.C. 471.025 AND 481.221.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 NEW SERVICE SHOWN?
  
 3) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
 EXISTING?
  
 4) PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
 PLEASE NOTE THAT PLANS ARE SHOWING ALL
 EXISTING ROOMS WITH NEW ELECTRIC? IF
 EXISTING EGRESS LIGHTING IS PRESENT
 PLEASE CLARIFY. NOTE FRONT DOOR W/ TWO
 SWITCHES SHOWN CONTROLLING ??
 PLEASE NOTE NEW FAMILY ROOM W/ SWITCH GO
 ING TO NEW FAN, DOES THIS HAVE A LIGHT
 KIT??
  
 5)NOTE: PLEASE NOTE THAT MECHANICAL
 PLANS AND ELECTRICAL PLANS DO NOT CORREL
 ATE. PLEASE NOTE THAT TWO A/C SYSTEMS
 ARE SHOWN ON A/C PLANS AND ONLY ONE
 ON ELECTRICAL LOAD CALCULATION AND PLANS
 PLEASE SHOW SECOND SYSTEM AHU AND CU.
 PLEASE SHOW DISCONNECTS PER 440-11. AND
 ANY REQ`D OUTLETS PER 210-63 AND 309.1.
  
 6)NOTE: PLEASE NOTE THAT THE ELECTRICAL
 LEGEND SHOWS LOW VOLTAGE ITEMS. THIS IS
 JUST A NOTE, BUT IF THERE IS GOING TO BE
 TELEPHONE OR CATV IN HOUSE THEN IT NEEDS
 TO BE ON PLANS FOR NEW ADDITION.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLANREVIEW
 561-659-8096 EXT 8372