Plan Review Notes
Plan Review Notes For Permit 01050299
Permit Number 01050299
Review Stop P
Sequence Number 2
Notes
Date Text
2001-06-18 00:00:00REVIEW NOTES:PASSED
  
 PROVISO:
  
 1)BACKFLOW REQUIRED TO BE MAXIMUM OF
 4' ABOVE FINISHED FLOOR FOR MAINTENANCE.
  
 2) BACKFLOW ALSO REQUIRES A FLOOR SINK
 TO DRAIN INTO, WITH A TRAP-PRIMER TO
 KEEP TRAP SEAL.
  
 3) PROVIDE DETAIL FOR ABOVE INSTALLATION
 THAT IS SIGNED AND SEALED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377