| Plan Review Notes For Permit 01050299 |
| Permit Number |
01050299 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-06-18 00:00:00 | REVIEW NOTES:PASSED | | | | | | PROVISO: | | | | | | 1)BACKFLOW REQUIRED TO BE MAXIMUM OF | | | 4' ABOVE FINISHED FLOOR FOR MAINTENANCE. | | | | | | 2) BACKFLOW ALSO REQUIRES A FLOOR SINK | | | TO DRAIN INTO, WITH A TRAP-PRIMER TO | | | KEEP TRAP SEAL. | | | | | | 3) PROVIDE DETAIL FOR ABOVE INSTALLATION | | | THAT IS SIGNED AND SEALED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|