Plan Review Notes
Plan Review Notes For Permit 01050299
Permit Number 01050299
Review Stop P
Sequence Number 1
Notes
Date Text
2001-05-27 00:00:00PLUMBING PLAN REVIEW"DENIED"
 (1) SHT A9.1 DOOR SWING IN RM'S #523 &
 #535,TO COMPLY W/FACBC 4.23.2 SWING DOOR
 OUT OF TURNING RADIUS OF WHEEL CHAIR.
 (2) SHT A9.2 DR'S OFFICE REST RM # 518
 TO BE ADAPTABLE, SHOW BACKING FOR GRAB
 BARS,DIMENSIONS OF FIXTURES OFF WALL.
 FACBC 97 SEC 4.1.3(11).
 (3) SHT A9.1 BREAK RM SINK RM #522,SHOW
 CLEAR FLOOR SPACE, COUNTER HGTH 34"FF.
 FACBC 97 SEC 4.24.2,4.24.5
 (4) SHT M-1 RM#525,NOTE 7,HUMIDIFIER
 WTER SUPPLY,TO BE PROTECTED WITH A BACK
 FLOW PREVENTER."RPZV".
 SPC 94 SEC 601.6
 END OF COMMENTSPAUL SCHMITZ