| Plan Review Notes For Permit 01050299 |
| Permit Number |
01050299 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-05-27 00:00:00 | PLUMBING PLAN REVIEW"DENIED" | | | (1) SHT A9.1 DOOR SWING IN RM'S #523 & | | | #535,TO COMPLY W/FACBC 4.23.2 SWING DOOR | | | OUT OF TURNING RADIUS OF WHEEL CHAIR. | | | (2) SHT A9.2 DR'S OFFICE REST RM # 518 | | | TO BE ADAPTABLE, SHOW BACKING FOR GRAB | | | BARS,DIMENSIONS OF FIXTURES OFF WALL. | | | FACBC 97 SEC 4.1.3(11). | | | (3) SHT A9.1 BREAK RM SINK RM #522,SHOW | | | CLEAR FLOOR SPACE, COUNTER HGTH 34"FF. | | | FACBC 97 SEC 4.24.2,4.24.5 | | | (4) SHT M-1 RM#525,NOTE 7,HUMIDIFIER | | | WTER SUPPLY,TO BE PROTECTED WITH A BACK | | | FLOW PREVENTER."RPZV". | | | SPC 94 SEC 601.6 | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096 X8233 |
|