| Plan Review Notes For Permit 01050299 |
| Permit Number |
01050299 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-05-29 00:00:00 | **************DENIED******************* | | | | | | 1. VERIFY EXISTANCE OF BASE BLDG. | | | EXHAUST RISER | | | 2. A/C 4 AND 5 CFM ON PLAN DO NOT | | | MATCH SCHEDULE FOR CFM | | | 3. SCHEDULE DOES NOT SHOW A/C 6 SHOWN ON | | | PLAN | | | 4. LEIBERT (A/C 6?) SHOWS DUCTS TO | | | CONDENSER OF A/C . FL. ENERGY CODE | | | 407.1.ABC D.3.3 DOES NOT PERMIT THE | | | CONDENSING COILS OF ONE UNIT TO BE IN | | | THE COOL AIR STREAM OF ANOTHER A/C UNIT. | | | 5. PROVIDE OUTSIDE AIR PER ASHRAE 62-89 | | | 6. PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE WITH 1997 SMC 501.2 | | | 7. NO COMBUSTIBLES ALLOWED IN R/A PLENUM | | | AREA INCLUDING PVC. |
|