2001-05-23 00:00:00******************PROVISO***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 WITH MECHANICAL PERMIT APPLICATION.
  
 1.OUTSIDE AIR CALCUTATIONS AS PER
 ASHRAE 62-89.
  
 2.SIZE OF SUPPLY DUCT IN BREAK/COPY/
 STORAGE ROOM, AND CFM TO THIS SPACE
 AS WELL AS THE DMG OFFICE.
  
  
 NOTE:NO COMBUSTIBLES ABOVE CEILING IN
 RETURN AIR PLENUM AS PER 1997
 SMC 609.1.1.
  
 FIRE DAMPERS SHALL COMPLY WITH
 REQUIREMENTS OF UL 555 AND SHALL
 BEAR THE LABLE OF AN APPROVED
 TESTING AGENCY. (1997 SMC
 610.1.1)
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8333.