| Plan Review Notes For Permit 01050294 |
| Permit Number |
01050294 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-05-23 00:00:00 | ******************PROVISO*************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | WITH MECHANICAL PERMIT APPLICATION. | | | | | | 1.OUTSIDE AIR CALCUTATIONS AS PER | | | ASHRAE 62-89. | | | | | | 2.SIZE OF SUPPLY DUCT IN BREAK/COPY/ | | | STORAGE ROOM, AND CFM TO THIS SPACE | | | AS WELL AS THE DMG OFFICE. | | | | | | | | | NOTE:NO COMBUSTIBLES ABOVE CEILING IN | | | RETURN AIR PLENUM AS PER 1997 | | | SMC 609.1.1. | | | | | | FIRE DAMPERS SHALL COMPLY WITH | | | REQUIREMENTS OF UL 555 AND SHALL | | | BEAR THE LABLE OF AN APPROVED | | | TESTING AGENCY. (1997 SMC | | | 610.1.1) | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8333. |
|