Plan Review Notes
Plan Review Notes For Permit 01050173
Permit Number 01050173
Review Stop P
Sequence Number 1
Notes
Date Text
2001-05-09 00:00:00REVIEW NOTES:PASSED
  
 *** PLUMBING NOTES ***
  
 PAGE A-1 PLUMBING NOTES #16 AIR CHAMBERS
 MUST COMPLY WITH SPC-94 607.8.2 AND
 607.8.3, MUST BE ACCESSABLE AND RECHARG-
 ABLE.
  
 PAGE A-1 PLUMBING NOTES #19 SPC-94 PIPE
 2" AND SMALLER SHALL BE INSTALLED WITH
 FALL OF 1/4" PER FOOT. 705.2
  
 SPC-94 TABLE 714.1, 3" PIPE (FOOTNOTE-3)
 NOT MORE THAN 2 W/C'S ALLOWED ON 3"
 SANITARY.
  
 SPC-94 MODEL COUNTYWIDE AMMENDMENTS TO
 CODE 607.7 "NO MORE THAN 2 FIXTURES
 SHALL BE SUPPLIED WITH A 1/2" COLD WATER
 SUPPLY. NO MORE THAN 4 FIXTURES SHALL BE
 SUPPLIED WITH A 1/2" HOT WATER SUPPLY.
  
 REVIEW BY KEN STEVENS (561) 659-8096
 EXT. 8377