Plan Review Notes
Plan Review Notes For Permit 01050154
Permit Number 01050154
Review Stop M
Sequence Number 3
Notes
Date Text
2001-07-23 00:00:00******************PROVISO***************
  
  
 MINIMUM OF 24" BETWEEN EXHAUST AND FRESH
 AIR INTAKE (1997 SMC 405) AND 10' FROM
 ANY ADJACENT BUILDING, PARKING AREA,
 PROPERTY LINE, WINDOW, DOOR AND ABOVE
 THE AADJOINING GRADE LEVEL (1997 SMC
 506.1
  
 MINIMUM OF 30" CLEAR SPACE ON SERVICE
 SIDE OF CONDENSER FOR INPECTION AND
 SERVICING.
  
  