| Plan Review Notes For Permit 01050154 |
| Permit Number |
01050154 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-06-15 00:00:00 | *******************DENIED*************** | | | | | | PLEASE PROVIDE OUTSIDE AIR CALCULATIONS | | | AS PER ASHRAE 62-89. | | | | | | PLEASE PROVIDE AIR BALANCE SCHEDULE AS | | | PER 1997 SMC 501.2. | | | | | | DUCTS PENETRATING RATED WALLS, REQUIRE | | | FIRE DAMPERS AS PER 1997 SMC 610.1.1 | | | PLEASE SHOW DUCT ON PLANS AS WELL AS | | | ANY FIRE DAMPERS. | | | | | | CONDENSATE SHALL COMPLY WITH 1997 SMC | | | 304.8.3, UNITS LARGER THAN 3 TON SHALL | | | DRAIN INTO STORM DRAIN OR AN APPROVED | | | DRY WELL. | | | | | | NOTE:SHOULD CONDENSERS BE MORE THAN | | | 20 FT ABOVE GRADE, THEY SHALL BE | | | ACCESSIBLE BY A PERMENANT MEANS. | | | | | | FM 200 FIRE SUPRESSION SYSTEM | | | REQUIRES SEPERATE PLANS & PERMIT | | | BY A LICENSED MECHANICAL | | | CONTRACTOR. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|