2001-06-15 00:00:00*******************DENIED***************
  
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER ASHRAE 62-89.
  
 PLEASE PROVIDE AIR BALANCE SCHEDULE AS
 PER 1997 SMC 501.2.
  
 DUCTS PENETRATING RATED WALLS, REQUIRE
 FIRE DAMPERS AS PER 1997 SMC 610.1.1
 PLEASE SHOW DUCT ON PLANS AS WELL AS
 ANY FIRE DAMPERS.
  
 CONDENSATE SHALL COMPLY WITH 1997 SMC
 304.8.3, UNITS LARGER THAN 3 TON SHALL
 DRAIN INTO STORM DRAIN OR AN APPROVED
 DRY WELL.
  
 NOTE:SHOULD CONDENSERS BE MORE THAN
 20 FT ABOVE GRADE, THEY SHALL BE
 ACCESSIBLE BY A PERMENANT MEANS.
  
 FM 200 FIRE SUPRESSION SYSTEM
 REQUIRES SEPERATE PLANS & PERMIT
 BY A LICENSED MECHANICAL
 CONTRACTOR.
  