| 2001-06-14 00:00:00 | ***************** UNSAT ************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT AS PER OVERVIEW |
| | AND CONVERSATION WITH WILLIAM STAPLES |
| | ASS BUILDING OFFICAL. PLEASE CONTACT |
| | DON NEELY IN REFERENCE TO LETTER ATTACHE |
| | D FOR ALL INSPECTIONS INCLUDING FINAL TO |
| | BE DONE BY MAURICE SHASHOUA P.E. |
| | DON NEELY'S EXT IS 8333 |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | PLEASE NOTE THAT NOTE ADDED TO PLANS ON |
| | E-1. PLANS CALL FOR 10,000 RATED BRKRS |
| | STILL MISSING RATINGS FOR ALL EQUIPMENT |
| | PER FIRST REVIEW. |
| | |
| | 3)NOTE: PLEASE NOTE THAT AS OF THIS |
| | REVIEW, LOAD CALCULAITONS WERE NOT |
| | SUBMITTED FOR REVIEW. PLEASE DO NOT |
| | RESUB NEXT TIME W/OUT LOAD CALCUALTIONS |
| | ON PLANS FOR EXSITING LOADS AND ALL NEW |
| | LOADS BEING ADDED. |
| | |
| | 4)NOTE: PLEASE NOTE THAT ALL CONTINUOUS |
| | LOADS NEED TO BE SHOWN AT 125%. INCLUD- |
| | -ING LOAD CALCS SUBMITTED. PER215-5,215- |
| | -3 AND 230-42 |
| | |
| | 5) PLEASE NOTE MISSING OUTLET FOR A/C |
| | EQUIPMENT PER 210-63 OF NEC AND 309.1 |
| | MECHANICAL CODE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. |
| | PLEASE NOTE THAT ALL OTHER ELECTRICAL |
| | CODE VIOLATIONS DISCOVERED BY |
| | CAPT MIKE CARSILLO DURING A FIELD |
| | INSPECTION WILL NEED TO BE CORRECTED |
| | BEFORE FINAL. SEPARATE PERMIT WILL BE |
| | REQ`D AND THAT SHOULD BE WORKED OUT |
| | WITH BLDG OWNER. |