Plan Review Notes
Plan Review Notes For Permit 01050154
Permit Number 01050154
Review Stop E
Sequence Number 2
Notes
Date Text
2001-06-14 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT AS PER OVERVIEW
 AND CONVERSATION WITH WILLIAM STAPLES
 ASS BUILDING OFFICAL. PLEASE CONTACT
 DON NEELY IN REFERENCE TO LETTER ATTACHE
 D FOR ALL INSPECTIONS INCLUDING FINAL TO
 BE DONE BY MAURICE SHASHOUA P.E.
 DON NEELY'S EXT IS 8333
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT NOTE ADDED TO PLANS ON
 E-1. PLANS CALL FOR 10,000 RATED BRKRS
 STILL MISSING RATINGS FOR ALL EQUIPMENT
 PER FIRST REVIEW.
  
 3)NOTE: PLEASE NOTE THAT AS OF THIS
 REVIEW, LOAD CALCULAITONS WERE NOT
 SUBMITTED FOR REVIEW. PLEASE DO NOT
 RESUB NEXT TIME W/OUT LOAD CALCUALTIONS
 ON PLANS FOR EXSITING LOADS AND ALL NEW
 LOADS BEING ADDED.
  
 4)NOTE: PLEASE NOTE THAT ALL CONTINUOUS
 LOADS NEED TO BE SHOWN AT 125%. INCLUD-
 -ING LOAD CALCS SUBMITTED. PER215-5,215-
 -3 AND 230-42
  
 5) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.
 PLEASE NOTE THAT ALL OTHER ELECTRICAL
 CODE VIOLATIONS DISCOVERED BY
 CAPT MIKE CARSILLO DURING A FIELD
 INSPECTION WILL NEED TO BE CORRECTED
 BEFORE FINAL. SEPARATE PERMIT WILL BE
 REQ`D AND THAT SHOULD BE WORKED OUT
 WITH BLDG OWNER.
 IF THERE ARE ANY QUESTIONS AND/OR A
 REQUEST FOR FEILD MEETING IS NEEDED,
 PLEASE CALL.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 JAKE LEAHY
 CHIEF ELECTRICAL INSPECTOR
 561-659-8096 EXT 8451