| Plan Review Notes For Permit 01050154 |
| Permit Number |
01050154 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-05-21 00:00:00 | ********************DENIED************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | | | | | | | 1.HOW ARE CONDENSER UNITS BEING | | | SECURED TO PLATFORM AND INDICATE | | | HOW UNITS WILL BE ACCESSED FOR | | | SERVICE.A MINIMUM OF 30" OF | | | CLEAR SPACE ON THE SERVICE SIDE | | | FOR INSPECTION AND SERVICE.(1997 | | | SMC 304.2.5.) | | | | | | 2.PROVIDE OUTSIDE CALCULATIONS AS PER | | | ASHRAE 62-89. | | | | | | 3.OVER FLOW PROTECTION AS PER 1997 | | | SMC 304.8.6, FOR THE FAN COIL. | | | | | | 4.PLEASE DESIGNATE WHERE CONDENSATE | | | TERMINATION WILL BE MADE. | | | NOTE, CONDENSATE SHALL NOT | | | TERMINATE INTO THE SANITARY.5 TON | | | SHALL DRAIN INTO STORM DRAIN OR | | | AN APPROVED FRENCH DRAIN. (1997 | | | SMC 304.8.3) | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096EXT.8388. |
|