| 2001-05-08 00:00:00 | 1) IT APPEARS THAT EQUIPMENT IS RUNNING | | | THROUGH THE EXIT STAIRWAY OR EXIT | | | CORRIDOR. NO PENETRATIONS ARE ALLOWED | | | TO ENTER THE EXIT STAIRWAY UNLESS IT | | | IS FOR FIRE PROTECTION OR EMERGENCY | | | LIGHTING. PLEASE CLARIFY AND NOTE THIS | | | ON THE DRAWINGS. | | | 2) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE INSTALLATION OF THE FM 200 | | | SYSTEM. THIS SYSTEM SHALL NOT BE IN | | | LIEU OF ANY REQUIRED FIRE SPRINKLER | | | PROTECTION. | | | 3) PLEASE EXPLAIN EXISTING CONDUIT UP | | | STAIRWAY SHOWN ON ELECTRICAL RISER | | | DIAGRAM DRAWING. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|