Plan Review Notes
Plan Review Notes For Permit 01050154
Permit Number 01050154
Review Stop E
Sequence Number 1
Notes
Date Text
2001-05-11 00:00:00******************* UNSAT ************
  
 1)NOTE: PLEASE PROVIDE LOAD
 CALCULATIONSFOR EXISTING MAIN. 215-5
  
 2)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT
 #`S ON PLANS THAT CORRELATE WITH
 SUBMITTED PANEL SCHEDULES.
  
 3)NOTE: PLEASE CLARIFY SIZE OF NEW
 TRAN--SFER SWITCH,, IS IT THE SAME AS
 EXISTING?
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372