Plan Review Notes
Plan Review Notes For Permit 01050121
Permit Number 01050121
Review Stop P
Sequence Number 1
Notes
Date Text
2001-05-25 00:00:00PLUMBING PLAN REVIEWDENIED
 (1) SHT AS-5 H/C REST RM IS NOT IN
 COPLIANCE W/FACBC-97,SEC 4.16.2
 WATERCLOSETS NOT IN A STALL,SEE FIG28
 ATTACHED.
 (2) SINKS COMPLY W/FACBC-97 SEC 4.24
 CLEAR FLR SPACE, SEE FIG 32 ATTACHED.
 (3) SPC-94 FLOOR DRAINS SEC 409.4 REQ.
 WITH TRAP PRIMER.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS 561-659-8096 X 8233