| Plan Review Notes For Permit 01050121 |
| Permit Number |
01050121 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-05-17 00:00:00 | SHEET AS1 UNDER NOTES DESIGN LOADS. | | | THIS FACILITY SHOULD BE A CATEGORY IV | | | AND NOT THE CATEGORY CATEGORY II | | | DECLARED.IT IS AN ESSENTIAL PUBLIC | | | UTILITY. | | | | | | THERE ARE NO SPECIFICATIONS FOR THE | | | METAL BUILDING ON THE PLANS NOR SPEC | | | BOOKS INCLUDED FOR REVIEW. | | | | | | THE GLAZING MUST MEET THE CITY'S HURRIC | | | ANE MISSILE IMPACT RESISTANCE POLICY. | | | | | | SECTION AS2 SHEET AS 7 "SECURE PER PLANK | | | MANUFACTURER'S RECOMMENDATIONS" IS NOT | | | AN ACCEPTABLE SUBSTITUTE FOR SPECIFC | | | DESIGN INFORMATION. | | | | | | TEST RPORTS AND DATA FOR THE WINDOWS, | | | DOORS AND ROOF COVERING SHOULD BE | | | PROVIDED WITH THE PERMIT APPLICATION. |
|