| 2001-08-01 00:00:00 | ****************** UNSAT *************** | | | | | | PLEASE NOTE THAT NOT ALL NOTES FROM | | | FIRST REVIEW WERE ADDRESSED. | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | | | | PLEASE REVISE AND SUBMIT THE ABOVE FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|