2001-08-01 00:00:00RE: THE BUTLER MFG. LETTER FROM J. E.
 LAMB.WHAT IS THE REFERENCE TO
 CLIMATIC DATA AND MBMA?WIND PRESSURE
 DESIGN MUST BE FROM ASCE 7-95 OR SBC
 1606.1.1.
  
 PROVIDE A SKETCH DEPICTING THE PRESSURE
 ZONES FOR THE COMPONENTS AND CLADDING
 THAT CORRELATE TO THE BUTLER SPECIFIC
 REACTION DRAWINGS.
  
 THE MIAMI DADE NOA #99-0318.03 IS
 MISSING THE DRAWING REFEREDCED IN
 SPECIFIC CONDITION #2. AND 6.1.2.
  
 NOA #00-0315.03 IS MOSTLY ILLEGIBLE AND
 HAS MISSING PAGES.