| Plan Review Notes For Permit 01050105 |
| Permit Number |
01050105 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-05-14 00:00:00 | 1) PLEASE INDICATE WHAT ACTIVITIES WILL | | | OCCUR IN THE COVERED WORK AREA, | | | WAREHOUSE, AND TECH AREA. | | | 2) PLEASE PROVIDE OCCUPANT LOAD | | | CALCULATIONS AND A LIFE SAFETY PLAN | | | FOR THE NEW BUILDING. | | | 3) PLEASE EXPLAIN NEW GATES. THESE GATES | | | MUST PROVIDE AT LEAST 20 FEET IN CLEAR | | | WIDTH FOR FIRE RESCUE ACCESS. WILL THE | | | GATES BE MANUAL OR ELECTRICALLY | | | OPERATED. | | | 4) PLEASE EXPLAIN EXITING RATIONALE FOR | | | THE NEW BUILDING. IT APPEARS THAT THE | | | CHAIN LINK FENCE LIMITS EXITING FROM | | | CERTAIN AREAS OF THE BUILDING. | | | 5) IS THE EXISTING BUILDING AND NEW | | | BUILDING GOING TO BE THE SAME TENANT. | | | 6) OPERABLE WINDOWS ARE TO BE PROVIDED | | | SO THE BUILDING WILL NOT BE CLASSIFIED | | | AS WINDOWLESS AND BE REQUIRED TO BE FIRE | | | SPRINKLER PROTECTED. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|