| Plan Review Notes For Permit 01050105 |
| Permit Number |
01050105 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-05-15 00:00:00 | ****************** UNSAT ************* | | | | | | 1)NOTE: PLEASE CLARIFY SERVICE ON PANEL | | | SCHEUDULE. SHOWS,, MAIN 800 AMP ? | | | TYPE-O? | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | RISER DIAGRAM SHOWS 200A AND 400K? | | | PLEASE CLARIFY. | | | | | | 3)NOTE: PLEASE SHOW ALL CONTINOUS LOADS | | | AT 125% (LIGHTING ETC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|