Plan Review Notes
Plan Review Notes For Permit 01050105
Permit Number 01050105
Review Stop B
Sequence Number 1
Notes
Date Text
2001-05-21 00:00:00WHAT IS THE CONSTRUCTION TYPE OF THE
 EXISTING BUILDING?SEE SBC 601.2.
  
 TYPE IV BUILDINGS INSIDE THE FIRE
 DISTRICT ARE REQUIRED TO HAVE 2 HR
 RATRED WALLS.SEE SBC F102.2.6.
  
 WHAT KIND AND QUANTITIES OF MATERIALS
 WILL BE STORED AND / OR USED IN THIS
 BUILDING?WHAT KIND OF MANUFACTURING
 PROCES SES ARE INTENDED?
  
 WHERE WILL THE DESIGN LOADS CALLED OUT
 ON S1 BE APPLIED TO THIS BUILDING?
  
 PROVIDE A SKETCH OR NOTES SHOWING THE
 WIND PRESSURE ZONES FOR THIS BUILDING
  
 PLEASE PROVIDE A PROPERTY SURVEY
  
 SHOW HOW THE GLAZED OPENINGS WILL COMPLY
 WITH THE CITY'S HURRICANE MISSILE
 IMPACT RESISTANCE POLICY.
  
 IMPACT FEES MUST BE PAID TO THE COUNTY.
 CALL 233-5025 FOR MORE INFORMATION.
  
 PROVIDE THE PRODUCT EVALUATION REPORTS
 FOR THE DOORS WINDOWS AND ROOF
 COVERINGS TO BE USED ON THIS BUILDING.