 BUILDING PLAN REVIEW
 PERMIT: 01050088
 ADD: 500 BAKER DR
 CONT: O/B GRAANTLEY RILEY
 TEL: (561) 6684-1620
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ****REVISION****
 DATE : 07/07/02
 1) PLANS INDICATE THEY ARE @ 140 MPH
 UNDER THE 1997 SBC,NO THEY ARE STILL
 110 MPH FOR THE 1997 CODE.
  
 2) THERE IS A DISCREPANCY IN THE PLANS:
 A) THE CUT SECTION OF THE WALL AND
 FLAT ROOF FRAMING MEMBERS 2X8 VS THE
 ROOF FRAMING AS 2X10@ 2'-0" O.C. THE
 PLANSDO NOT GIVE THE SPECIES OF WOOD,
 NOR THE GRADE OF WOOD TO BE USED.
 USING RAFTER TABLES FOR 30 LBS LIVE LOAD
 & 20 LBS DEAD LOAD, SPANNING 13'-0"@
 2'-0" O.C.= REQUIRES 2"X10".
  
 3) TO MAKE A REVISION ON THE EXT. WALL
 FROM 2X6 TO 2X4 THE PLANS STILL SHOW A
 2X6 PT BOTTOM PLATE.
  
 4) THIS PLAN REVIEW WAS COMPLETED UNDER
 THE PRESCRIPTIVE CODE FOR STANDARD FOR
 HURRICANE RESISTANT RESISIDENTIAL CONST
 SSTD 10-97, ANCHOR BOLTS TABLE 303.3.2
 REQUIRES ANCHOR BOLTS @ 1'-6" O.C.,
 FIGUE 303E INDICATES THE MINIMUM EMBED-
 MENT IN CONCRETE IS 7" NOT THE OVERALL
 LENGTH.
  
 5) SINCE THE EXTERIOR WALL IS NOW A
 2X4 THE ENERGY CALCS MUST ALSO RELEECT
 THE NEW R-11 INSULATION NOT R-19.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026