Plan Review Notes
Plan Review Notes For Permit 01050088
Permit Number 01050088
Review Stop B
Sequence Number 1
Notes
Date Text
2001-05-08 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01050088
 500 BAKER DR
 O/B RILEY,GRANTLEY
 1)- PLANS HAVE DISCPEPANCIES:
 A) IN DIMENSIONS FLOOR PLAN VS.REAR ELE
 B) 12'-0" WINDOWS ON FLOOR PLAN OF ADD.
 VS. REAR ELEVATION
  
 2)- PLANS ARE TO BE DESIGNED TO THE SBC
 SSTD 10-97 HURRICANE RESISTANT
 RESIDENTIAL CONSTRUCTION.
  
 3)- MONOLITHIC SLAB TO SHOW THE SIZE OF
 STEEL TO BE USED. VAPOR BARRIER & TER-
 MITE TREATMENT. THE FOUNDATION MUST BE
 12" BELOW GRADE, THE SLAB A MINIMUM OF
 4" ABOVE GRADE, SUBSHEATHING MUST BE 6"
 ABOVE GRADE OR PRESSURE TREATED WOOD
 WHEN WITHIN 6" OF GRADE. ANCHOR BOLTS,
 THE SIZE NOR SPACING IS GIVEN.
  
 4)- STUDWALLS: THERE IS NO INFORMATION
 ON TOP & BOTTOM PLATE STRAPPING,MANUFAC-
 TURE, MODEL OR CAPACITIES. THE SPECIES
 OF WOOD IS NOT GIVEN NOR IS THE SPACING
 OF THE STUDS. NO DETAILS ON SHEARWALL
 SEGMENTS, HOLD DOWN BRACKETS AT OPENINGS
 NOR WALL TO RAFTER CONNECTIONS.
  
 5) CEILING JOIST: SPECIES OF WOOD, GRADE
 OF WOOD NOT GIVEN, SIZE OF WOOD NOT
 GIVEN, GIVE SPACING & SPAN. GIVE LIVE
 & DEAD LOADS. THE OTHER END OF THE CEIL-
 ING JOIST IS NOT GIVEN, ATTACHMENT DE-
 TAIL.
  
 6) RAFTERS: ARE TO BE 2X10 PER PLAN, THE
 PLAN CALLS FOR 6'-0" O.C.--NO-- GIVE
 THE SPECIES OF WOOD, GRADE, SIZE OF
 TIMBER & THE SPACING, LIVE & DEAD LOADS
 AND SPAN TO DETERMINE THE SIZE OF TIMBER
 VS. THE SPAN!!!!
  
 7) ROOFING MATERIAL: ASPHALT SHINGLES
 --NO--- THE PLAN CALLS FOR A 1:12 PITCH
 THIS IS TO LOW OF A SLOP FOR SHINGLES.
  
 8) GLAZED OPENINGS & DOORS WILL REQUIRE
 PRODUCT APPROVAL FOR WIND, WINDOWS WILL
 REQUIRE TESTING REPORTS FOR LARGE MISSLE
 IMPACT TESTING, DADE COUNTY OR SBCCI RE
 PORT WILL BE ACCEPTABLE.
  
 9) ROOFING MATERIALS WILL ALSO REQUIRE
 PRODUCT TESTING REPORT FOR 110 MPH WIND
 SBCCI OR DADE COUNTY REPORT ARE ACCEPT-
 ABLE.
  
 10) COUNTY IMPACT FEES FOR THE ADDITION-
 AL FOOTAGE THAT IS ADDED.
  
 JIM WITMER
 BUILDING PLAN REVIEW
 (561)659-8096 EX 8412