| 2001-06-06 00:00:00 | *************BUILDING UNSAT************* |
| | |
| | 1)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - EXTERIOR WINDOWS |
| | - EXTERIOR DOORS |
| | - GARAGE DOOR |
| | - STORM PANELS |
| | - GLASS BLOCK |
| | |
| | 2) PROVIDE (2) PRODUCT APPROVALS, KEY |
| | PLANS AND INSTALLATION SCHEDULES |
| | INDICATING THE SPECIFIC TYPES OF ANCHORS |
| | TO BE USED FOR STORM PANELS. |
| | |
| | 3) PROVIDE SOIL TEST PER SEC. 1804.2.2 |
| | OF CITY AMENDMENTS TO 1997 SBC. |
| | |
| | 4) PROVIDE ENERGY CALCULATIONS AND |
| | MANUAL "J" CALCULATIONS PER 97 FLORIDA |
| | ENERGY CODE FOR BUILDING CONSTRUCTION. |
| | |
| | 5) WALL SECTIONS 4&5 ON A-6 INDICATE |
| | R-13 INSULATION AND THE FLOOR PLAN ON |
| | A-2 INDICATES R-11 INSULATION PLEASE |
| | CORRECT. |
| | |
| | 6) THE SCALES GIVEN FOR THE ELEVATIONS |
| | ON A-3 ARE INCORRECTLY LISTED AS 1/8" = |
| | 1'-0". PLEASE CORRECT. |
| | |
| | 7) PROVIDE CONSTRUCTION DETAILS FOR ARCH |
| | OPENINGS IN EXTERIOR WALLS. |
| | |
| | 8) PROVIDE DESIGN COMPLIANCE FORM TO |
| | INDICATE THE DESIGN PARAMETERS AND |
| | ASSUMPTIONS USED FOR THIS STRUCTURE. |
| | |
| | 9) SPACING OF VERTICLE WALL REINFORCE- |
| | MENT DOES NOT COMPLY WITH SSTD 10-97. |
| | PEASE REVIEW AND CORRECT, IF USING THE |
| | PRESCRIPTIVE METHOD OF DESIGN COMPLIANCE |
| | |
| | 10) PROVIDE DESIGN PARAMETERS AND |
| | ASSUMPTIONS USED TO DETERMINE FORCES AND |
| | REACTIONS APPLIED TO ROOF TRUSSES AND |
| | GIRDERS. |
| | |
| | 11) INDICATE THE TRUSS CONNECTORS THAT |
| | WILL BE USED ON THE TRUSSES THAT ARE NOT |
| | SPECIFICALLY INDICATED ON PLANS. |
| | |
| | 12) INDICATE MEAN ROOF HEIGHT ON PLANS. |
| | |