2001-06-18 00:00:00BUILDING COMMENTS
 2ND REVIEW
 ------------
 1]
 DCA LETTER REQUESTED STILL NOT PROVIDED.
 2]
 GENERAL STATEMENTS [LATEST EDITION IS
 NOT ACCEPTABLE],PLEASE BE SPECIFIC.ASCE
 7-93 IS NOT ACCEPTABLE.ALL STRUCTURAL
 CALCULATIONS AND COMPUTATIONS SHALL BE
 AS PER ASCE 7-95.
 3]
 PROJECT IS LOCATED ON CONGRESS AVE.
 EXPLAIN REFERENCE TO AUSTRALIA AVE.?
 4]
 COMMUTATIONS SUBMITTED ARE ACCORDING TO
 UBC 1997 AND ASCE 7-93,PLEASE REVISE AND
 SUBMIT CALCULATIONS AS PER ASCE 7-95.
 5]
 YOUR ON SITE ENGINEER/INSPECTOR SHALL BE
 APPROVED BY THE ASS. BUILD. OFFICIAL
 PRIOR TO PERMIT ISSUE.
  
  